Off-Grid Solar Calculator

Size a complete off-grid system from your daily loads: solar array, battery bank, charge controller and inverter, all in one place.

ApplianceWattsHours/day

How to use this off-grid solar calculator

List the appliances you run each day with their power in watts and how many hours per day they run. Add or remove rows to match your setup, then pick your system voltage, battery type, peak sun hours and days of autonomy. The calculator sizes the four core parts of an off-grid system at once.

  • Solar array — enough panels to refill your daily energy use during your available sun hours.
  • Battery bank — enough storage for your days of autonomy, adjusted for how deeply the battery can be discharged.
  • Charge controller — rated for the array's current with a safety margin.
  • Inverter — rated for your peak simultaneous AC load.

How the sizing works

daily energy (Wh) = sum of (watts × hours) for each appliance
array (W) = daily Wh ÷ peak sun hours ÷ 0.8 (system losses)
battery (Wh) = daily Wh × days of autonomy ÷ depth of discharge
battery (Ah) = battery Wh ÷ system voltage
controller (A) = array W ÷ system voltage × 1.25
inverter (W) = peak simultaneous load × 1.25

The 0.8 factor covers wiring, controller and temperature losses. Depth of discharge is how much of the battery you can safely use, about 80% for lithium and 50% for lead-acid, which is why lead-acid banks are sized larger.

Two battery limits the basic formula misses

Sizing the battery by watt-hours gets you the right capacity, but two real-world limits decide whether that capacity actually shows up when you need it.

Cold weather cuts usable capacity

The Ah figure above assumes a battery near room temperature. A LiFePO4 battery gives back noticeably less as it gets cold, and charging below freezing can damage it. If your bank sleeps in an unheated space, a van or an outdoor box, your real winter autonomy will fall short of the number here. Add margin, insulate or heat the battery, or plan to recharge more often in the cold. This calculator flags it in the result, and the cold-weather voltage check on the controller page covers the matching panel-side risk.

The bank must deliver your peak power, not just the energy

A battery's maximum continuous discharge is set by its cells and its BMS, roughly its capacity times a C-rate. A bank can hold plenty of energy yet still be unable to deliver your inverter's peak draw all at once, at which point the BMS cuts out. As a rough guide, continuous discharge watts ≈ bank Ah × system voltage × C-rate (conservatively about 0.5C for LiFePO4, 0.2C for lead-acid). The calculator compares this to your peak load and warns you if the bank looks too small to feed the inverter. Always confirm the real figure on your battery's spec sheet.

Frequently asked questions

Start from your daily watt-hours (watts × hours per appliance). Array = daily Wh ÷ peak sun hours ÷ 0.8. Battery = daily Wh × days of autonomy ÷ usable depth of discharge. Then size the controller from array watts and the inverter from your peak simultaneous load.
The hours per day when sunlight averages 1000 W/m². Most places get 3 to 6 depending on location and season. Size for your worst usable month.
How long the battery runs your loads with no sun. Two days is a common start; three or more is safer in cloudy climates but needs a bigger battery.
Under ~1 kWh/day, 12V is fine. Roughly 1 to 3 kWh/day, use 24V. Above that, 48V. Higher voltage means less current, so thinner wire and smaller controllers.
Yes. The Ah figure assumes a battery near room temperature. LiFePO4 delivers less as it gets cold, and charging below freezing can damage it. If your bank lives in an unheated space, real winter autonomy is lower than the estimate, so add margin, insulate or heat the battery, or recharge more often.
Not always. A battery's maximum continuous discharge is limited by its cells and BMS, roughly capacity × a C-rate (about 0.5C for LiFePO4, 0.2C for lead-acid). A bank can store enough energy yet still be unable to supply a big inverter surge, and the BMS then cuts out. Check continuous discharge watts ≈ bank Ah × voltage × C-rate against your peak load, and confirm on the spec sheet.

More SolarSizr calculators

Once you know your system size, set the panel angle, the wire size, the charge controller and the inverter size.