Solar Wire Size Calculator
Find the right wire gauge for your solar wiring. Enter your voltage, current, cable length and target voltage drop, and get the size in AWG and mm² with an ampacity safety check.
Recommended wire size
Nearby wire sizes for this run
| AWG | mm² | Voltage drop | Ampacity |
|---|
Ampacity shown is adjusted for the chosen material. A check mark means the wire can safely carry your current; a cross means it cannot.
How to use this solar wire size calculator
Enter four things and the calculator returns the right wire gauge instantly:
- System voltage — 12, 24 or 48 V for most DIY and off-grid solar.
- Current in amps — the maximum current the wire will carry (for a panel, use its short-circuit current Isc; for a load, its running current).
- Cable length, one way — the distance from source to load. The calculator doubles it automatically for the return path.
- Max voltage drop — 3% is the common target, 2% for critical runs.
The result is given in AWG (American Wire Gauge) and mm², and is checked against both voltage drop and ampacity. The thicker of the two wins.
How wire size is calculated
Two separate limits decide the wire size, and you must satisfy both.
1. Voltage drop
Thin wire and long runs waste energy as heat. The cross-section needed to stay within your voltage-drop target is:
where ρ is the resistivity of the metal (copper ≈ 0.0175, aluminium ≈ 0.0282 Ω·mm²/m) and the length is doubled to account for the return conductor.
2. Ampacity
Ampacity is the current a wire can carry continuously without overheating. Even a short run must meet it for safety. This tool uses a copper ampacity table for 90 °C-rated insulation (aluminium is derated by about 22%). On long runs, voltage drop usually demands a thicker wire than ampacity alone.
Temperature and code: why rated ampacity isn't the whole story
The ampacity figures in the table are for a conductor in a 30 °C (86 °F) ambient. Wire run in hot places, a roof in full sun, an engine bay, a conduit baking outdoors, carries less current safely, so its ampacity must be derated. Enter an ambient temperature above and the calculator applies the standard correction factor for 90 °C conductors; leave it blank to use the 30 °C baseline.
Two more rules that this planning tool does not fully model, and that your local code does:
- Termination rating. Breakers, lugs and many devices are only rated to 75 °C (sometimes 60 °C). The weakest link in the circuit sets the real limit, so you often cannot use the full 90 °C ampacity even with 90 °C wire.
- Bundling / conduit fill. Running several current-carrying conductors together derates them further, because they warm each other.
Treat the result as a starting point and size up when in doubt. For a real installation, follow the ampacity, correction and adjustment tables in your local electrical code (in the US, the NEC: ampacity Table 310.16, temperature correction 310.15(B)(1), and conductor adjustment 310.15(C)(1)), or have a licensed electrician confirm the run.
Why 12V systems need thick wire
Power equals voltage times current. For the same power, a 12 V system carries four times the current of a 48 V system, and voltage drop rises with current. That is why the same 200 W load needs far heavier cable at 12 V than at 48 V over the same distance. If your wire size comes out huge, raising the system voltage is often cheaper than buying massive cable.
Frequently asked questions
More SolarSizr calculators
Setting up a whole system? Try the off-grid solar calculator. You can also find the optimal panel angle and size your charge controller.