Solar Wire Size Calculator

Find the right wire gauge for your solar wiring. Enter your voltage, current, cable length and target voltage drop, and get the size in AWG and mm² with an ampacity safety check.

How to use this solar wire size calculator

Enter four things and the calculator returns the right wire gauge instantly:

  • System voltage — 12, 24 or 48 V for most DIY and off-grid solar.
  • Current in amps — the maximum current the wire will carry (for a panel, use its short-circuit current Isc; for a load, its running current).
  • Cable length, one way — the distance from source to load. The calculator doubles it automatically for the return path.
  • Max voltage drop — 3% is the common target, 2% for critical runs.

The result is given in AWG (American Wire Gauge) and mm², and is checked against both voltage drop and ampacity. The thicker of the two wins.

How wire size is calculated

Two separate limits decide the wire size, and you must satisfy both.

1. Voltage drop

Thin wire and long runs waste energy as heat. The cross-section needed to stay within your voltage-drop target is:

area (mm²) = (2 × length × current × ρ) ÷ (voltage × drop% ÷ 100)

where ρ is the resistivity of the metal (copper ≈ 0.0175, aluminium ≈ 0.0282 Ω·mm²/m) and the length is doubled to account for the return conductor.

2. Ampacity

Ampacity is the current a wire can carry continuously without overheating. Even a short run must meet it for safety. This tool uses a copper ampacity table for 90 °C-rated insulation (aluminium is derated by about 22%). On long runs, voltage drop usually demands a thicker wire than ampacity alone.

Temperature and code: why rated ampacity isn't the whole story

The ampacity figures in the table are for a conductor in a 30 °C (86 °F) ambient. Wire run in hot places, a roof in full sun, an engine bay, a conduit baking outdoors, carries less current safely, so its ampacity must be derated. Enter an ambient temperature above and the calculator applies the standard correction factor for 90 °C conductors; leave it blank to use the 30 °C baseline.

Two more rules that this planning tool does not fully model, and that your local code does:

  • Termination rating. Breakers, lugs and many devices are only rated to 75 °C (sometimes 60 °C). The weakest link in the circuit sets the real limit, so you often cannot use the full 90 °C ampacity even with 90 °C wire.
  • Bundling / conduit fill. Running several current-carrying conductors together derates them further, because they warm each other.

Treat the result as a starting point and size up when in doubt. For a real installation, follow the ampacity, correction and adjustment tables in your local electrical code (in the US, the NEC: ampacity Table 310.16, temperature correction 310.15(B)(1), and conductor adjustment 310.15(C)(1)), or have a licensed electrician confirm the run.

Why 12V systems need thick wire

Power equals voltage times current. For the same power, a 12 V system carries four times the current of a 48 V system, and voltage drop rises with current. That is why the same 200 W load needs far heavier cable at 12 V than at 48 V over the same distance. If your wire size comes out huge, raising the system voltage is often cheaper than buying massive cable.

Frequently asked questions

It depends on the current, the cable length and your system voltage. Longer runs and lower voltages need thicker wire to keep voltage drop under about 3%. Enter your numbers above to get the exact gauge in AWG and mm².
Aim for 3% or less on the main DC runs, and 2% or less on critical circuits such as panel-to-charge-controller. Lower drop wastes less energy but needs thicker, pricier wire.
Lower voltage means higher current for the same power, and voltage drop grows with current. A 12V system carries four times the current of a 48V system for the same watts, so it needs much thicker cable over the same distance.
Both. Ampacity sets the minimum for safety; voltage drop often demands an even thicker wire on long runs. This calculator checks both and recommends whichever is larger.
Yes. Rated ampacity assumes a 30 °C ambient. Wire in a hot spot, a roof in full sun or an outdoor conduit, carries less safely, so ampacity is derated by a temperature correction factor. Bundling conductors and 60 to 75 °C terminals reduce it further. Enter an ambient temperature to apply the 90 °C correction factor, and follow your local code for the rest.

More SolarSizr calculators

Setting up a whole system? Try the off-grid solar calculator. You can also find the optimal panel angle and size your charge controller.